4/2/2024 0 Comments Loopcad tutorial![]() It is also designed to get the room temperatures up within 60 minutes from memory - there is a set of parameters hidden somewhere and you can alter these. Yes but I expect the dT is something like 8c based on 45/37 which is the hot end and traditional flows. ![]() And if those same runs could go through the "NO UFH" room (with insulation) then that gives them a very much more direct route to the manifold. ![]() Just insulate the short sections of pipe going under the units. In the kitchen, I can see why you want no heating under the units but I would pass the pipes to and from loops 1-10, 1-11 and 1-12 under that peninsular run of units just to save the congestion going around the units. I am surprised bed 1 needs 2 loops I would be tempted to make that just one, that is another less port on the manifold and less congention in that hall. I take it the room left of the kitchen is a pantry hence no UFH? If you can pass pipes under the internal walls you can get some much better pipe runs Why only go through doorways? Why no UFH in the bathrooms? It is really nice to have a warm floor in the bathrooms. That will be all the heating you want in the hall. Instead just space out all the pipes that are passing through the hall. The landing one NEVER came on, and the hall one only very rarely. In our previous house on the advice of the UFH designer we had a loop in the hall and one on the landing.